What to Measure
On site you need supply and exhaust airflow, and dry-bulb (and wet-bulb for enthalpy) temperatures on both sides.
Procedure
- Balance and confirm airflow with a hood or pitot
- Log inlet and outlet temperatures on both streams for a stable period
- Record pressure drop across the core
Compute Effectiveness
Use the measured temperatures in the effectiveness formula. For enthalpy wheels include humidity.
Judge the Result
Compare the measured value with the rated curve at the same conditions. A large gap means fouling, leakage, or a wrong selection. Keep the sheet as the commissioning baseline.
Before You Start
A successful Measure Heat Recovery Performance On-Site project begins with measurement. Record the supply and exhaust airflow rates, the temperatures on each side, and the hours the system runs per year. Note any contaminants in the exhaust and the available space for the core and ductwork. These figures decide both the type of exchanger and whether the payback makes sense.
Step-by-Step
First, choose the exchanger type from the air cleanliness and recovery target. Second, size the core using the measured airflow and the log-mean temperature difference, leaving margin for fouling. Third, lay out the duct path so the exhaust is filtered before the core and the supply side has drainage if it may condense. Fourth, add a bypass for free cooling and wire the fans to a simple control. Finally, commission the unit and record baseline temperatures.
Verification
After startup, compare the pre- and post-installation supply temperatures at the same outdoor condition. A steady recovery of 50 percent or more confirms correct sizing. Re-check each season and clean the exhaust side when the recovered temperature begins to fall, because fouling quietly erodes performance over time.
Frequently Asked Questions
Do I need a bypass? In most climates yes, so the system can free-cool when outdoor air is mild. How is sizing done? From measured airflow and the log-mean temperature difference, not from estimates.
Practical Selection Checklist
For the Measure Heat Recovery Performance On-Site duty, confirm the measured airflow and the temperature difference between the two airstreams before specifying any unit. Choose the core type that matches the exhaust cleanliness and the recovery target, allow margin for fouling, and verify the pressure drop stays inside the fan curve. Place filtration ahead of the core and provide a condensate drain where the supply side may fall below the dew point.
When to Specify This Solution
Energy recovery suits any plant or building that expels warm exhaust continuously while drawing in fresh air that must be conditioned from ambient. Common candidates include make-up air units, drying rooms, commercial kitchens, paint booths, and general process ventilation. Where the annual cost of heating or cooling make-up air is material, a correctly sized exchanger usually pays back within one to three operating seasons.
Next Steps
Start by logging the supply and exhaust conditions for a full duty cycle, then size the core from those numbers rather than from nameplate estimates. Compare the projected energy saving with the equipment and installation cost to get a payback figure, and review the comparison and product guides for the specific configuration that fits your site.