The Core Formula
Recovered power Q = m_dot x cp x DeltaT x effectiveness, where m_dot is mass flow (kg/s), cp for air is about 1.006 kJ/kg.K, and DeltaT is the temperature difference between streams.
Worked Example
For a 10,000 m3/h stream (density 1.2 kg/m3 -> 3.33 kg/s) at a 20 K difference with 70 percent effectiveness: Q = 3.33 x 1.006 x 20 x 0.70 is about 46 kW removed from the fresh-air heating load.
From Power to Size
- Choose target effectiveness from the device type
- Pick face velocity from the manufacturer's band
- Face area = airflow / face velocity; core volume follows from depth
Don't Forget
- Use part-load average airflow, not peak, for realistic savings
- Add the extra fan power from pressure drop to the energy balance
- Include frost-protection energy in cold climates
Tools
Use our sizing spreadsheet or an online calculator to vary inputs and watch payback change before you commit to a size.