Step 1 - Audit the Duty
Record supply and exhaust airflow, indoor and outdoor design temperatures, and the allowable supply-air temperature. Confirm the streams are reasonably balanced.
Step 2 - Pick the Technology
- Simple, low-maintenance - crossflow plate core
- Highest effectiveness or humidity - rotary wheel
- Contaminated or separated streams - run-around coil
- Rugged, no moving parts - heat pipe
Step 3 - Check the AHU
- Physical space in or beside the unit
- Fan capacity for the added static pressure
- Controls for summer bypass and frost protection
Step 4 - Install
Slot the core into the AHU section, seal the interfaces, connect controls, and verify drainage for condensate.
Step 5 - Commission
Measure airflow and temperatures on both sides, compute actual effectiveness, and compare with the rated curve. Document the result as the baseline.